With the series ZPN, ZDPN and ZT, Baumer offers very robust pressure and temperature switches developed especially for use in nuclear power stations. The pressure switches are suitable for pneumatic or hydraulic control, for power generation safety equipment and for pressurized chamber control. They are resistant to short duration overpressure and show a good vibration resistance. The ZPN can measure a gauge pressure from -1 bar up to 600 bar with a very small intermediate range from -2 mbar up to 10 mbar. The ZDPN measures a differential pressure from 2 mbar up to 120 bar.
The pressure switches maintain a constant pressure around a chosen set value. When the pressure reaches a critical pre-set value, they trigger an alarm or safety system. A flexible diaphragm actuates a micro-switch via a piston. The set point adjustment is realised via a compressible spring mounted on the opposite. Due to the force-balance principle, the dead band setting remains constant, even with different set point adjustments. With rapid pressure variations, an attenuator should be used to prevent a temporary on- and off-switching.
The ZT temperature switches are suitable for all fluids and measuring ranges between -45°C and 350°C. They maintain a constant temperature around a chosen set value and act as regulator of an alarm or safety system when the temperature reaches a critical pre-set value.
The pressure and temperature switches ZPN, ZDPN and ZT offer a very good repeatability (±1% F.S.) making them suitable for all demanding applications. The devices comply with ATEX 94/9/CE requirements for the use in hazardous areas; they are available in an intrinsically safe and an explosion-proof version; and they are approved by the French electricity board EDF.
Source: automation.com
- 28/10/2009 22:43 - SICK releases CLV650 and CLV640 bar code scanners
- 21/10/2009 09:51 - Kepware releases KEPServerEX OPC Server Version 5.1
- 12/10/2009 15:37 - Emerson enhances diagnostic software for ultrasonic meters
- 12/10/2009 15:20 - Siemens announces Simatic PCS 7 Burner Management System
- 08/10/2009 23:26 - Siemens adds alarm management to Simatic PCS
- 02/10/2009 00:30 - Electric Fish Plug In To Communicate
- 01/10/2009 23:04 - Honeywell introduces Precision FotoFiber sensor for paper
- 29/09/2009 00:59 - Scientists Find Successful Way To Reduce Bat Deaths At Wind Turbines
- 29/09/2009 00:54 - Baumer announces MOR 90 /105 magnetic incremental encoders
- 29/09/2009 00:42 - Power plant control system platform designed for the very long term.